The v0.2.1 increment adds two new industrial transports — Modbus RTU and J1939 — while keeping protocol semantics in Nodra and hardware discovery/capture in Zyvor Device Agent.

Get the highlights.

  • 2
    New industrial transports added in v0.2.1 — Modbus RTU and J1939
  • 0x03
    Modbus function code the RTU transport implements for polling reads
  • 29-bit
    Extended CAN frame format decoded by the J1939 connector
  • CRC16
    Checked on every Modbus RTU response for transport integrity

This increment keeps protocol semantics in Nodra while Zyvor Device Agent owns only physical hardware discovery/capture.

Take a closer look

The existing modbus connector now accepts transport: "tcp" (default) or transport: "rtu".

{
  "type": "modbus",
  "name": "boiler-plc",
  "config": {
    "transport": "rtu",
    "device": "/dev/ttyS1",
    "baud": 9600,
    "data_bits": 8,
    "parity": "none",
    "stop_bits": 1,
    "unit_id": 1,
    "start": 0,
    "quantity": 8,
    "topic": "factory/boiler/plc/registers",
    "interval": "2s",
    "timeout": "1s"
  }
}

The RTU transport implements function 0x03 reads and shares the existing connector poll/publish path. CRC16 is checked on every response. Serial configuration uses Linux termios and opens the device per transaction for deterministic unplug/replug recovery.

The kernel/board is expected to own RS485 direction control. Nodra does not silently rewrite RS485 mode or scan unit IDs.

Enable read-only CAN capture in Device Agent, then add:

{
  "type": "j1939-device-agent",
  "name": "truck-can",
  "config": {
    "url": "http://127.0.0.1:9188/api/v1/can/frames/stream",
    "topic_prefix": "vehicle/j1939",
    "reconnect": "2s"
  }
}

The connector accepts only extended 29-bit data frames, derives priority/PGN/source/destination, and emits Nodra events such as:

vehicle/j1939/pgn/00F004
vehicle/j1939/pgn/00FF50

Standard CAN, RTR and CAN error frames are ignored. Nodra's normal ingest/WAL/local-route/cloud path remains unchanged.

Raw + decoded duplication: if j1939-device-agent consumes the Device Agent SSE stream, set Device Agent industrial.can_capture.publish_to_nodra = false when only decoded PGN events are desired. Keep it enabled only when both raw CAN archival topics and decoded J1939 topics are intentional.

A dependency-free, hand-rolled UA-TCP (binary) client, following the same dependency-free philosophy as the Modbus TCP building block. Scope is deliberately narrow:

  • SecurityPolicy None by default — anonymous session, no channel encryption or signing. Basic256Sha256 scaffolding is wired: set security_policy to Basic256Sha256, security_mode to Sign or SignAndEncrypt (default), and client_cert_path / client_key_path / server_cert_path. Without those cert paths the connector fails fast with an actionable error. Full secure-channel crypto (RSA-OAEP, PKCS#1/PSS signing, HMAC-SHA256 key derivation) is not shipped in this build yet — even with readable certs you get a clear "channel crypto is not available" error rather than a subtly wrong encrypted channel. Tracked in ROADMAP.md.
  • Anonymous session only — no username/password or certificate-based user tokens (independent of channel security policy).
  • Read and Subscribe/MonitoredItems — mode: "poll" (default) ticks Read on interval; mode: "subscribe" instead opens one long-lived Subscribe session and reconnects (waiting interval between attempts) on any error. This is the least-verified part of the package: unlike Read/Write/Browse's single-request-response shape, Subscribe's multi-step CreateSubscription/CreateMonitoredItems/Publish protocol has more surface for a subtle wire-format mistake to hide — smoke-test against a real server (e.g. open62541) before production use.
  • Values must decode as a scalar Boolean/Int16/UInt16/Int32/UInt32/ Int64/UInt64/Float/Double/String/DateTime; an array or unsupported Variant type fails that poll cycle (Read) or is rejected before sending (Write).
{
  "type": "opcua",
  "name": "boiler-plc",
  "config": {
    "endpoint": "opc.tcp://boiler-plc.local:4840",
    "node_ids": ["ns=2;i=1001", "ns=2;s=Temperature"],
    "topic": "factory/boiler/opcua",
    "interval": "5s",
    "timeout": "5s"
  }
}

Optional Basic256Sha256 config (fails until channel crypto lands; cert paths are required when this policy is selected):

{
  "type": "opcua",
  "name": "boiler-plc-secure",
  "config": {
    "endpoint": "opc.tcp://boiler-plc.local:4840",
    "node_ids": ["ns=2;i=1001"],
    "topic": "factory/boiler/opcua",
    "security_policy": "Basic256Sha256",
    "security_mode": "SignAndEncrypt",
    "client_cert_path": "/etc/nodra/opcua/client.crt",
    "client_key_path": "/etc/nodra/opcua/client.key",
    "server_cert_path": "/etc/nodra/opcua/server.crt"
  }
}

Each poll opens a fresh connection (Hello/Acknowledge, OpenSecureChannel, CreateSession, ActivateSession, Read, Close) rather than holding a session open across polls — the same per-call-dial pattern the Modbus TCP client uses.

Set "mode": "subscribe" instead of polling Read on an interval:

{
  "type": "opcua",
  "name": "boiler-plc-push",
  "config": {
    "endpoint": "opc.tcp://boiler-plc.local:4840",
    "node_ids": ["ns=2;i=1001", "ns=2;s=Temperature"],
    "topic": "factory/boiler/opcua",
    "mode": "subscribe",
    "interval": "1s",
    "timeout": "5s"
  }
}

This holds one connection open (CreateSubscription + CreateMonitoredItems for every configured node, then a continuous Publish loop) instead of dialing per tick — interval becomes the requested publishing interval and, separately, the reconnect backoff after an error. Each server- pushed value is emitted as its own event, one node per event, unlike mode: "poll"'s single event batching every configured node.

Only the Value attribute's data changes are monitored (no Events, filters, or non-Value attributes); QueueSize is 1 with DiscardOldest, so a burst of rapid changes only ever surfaces the latest value, not a backlog.

Write, discovery and Browse are Go Client/package-level API calls, not poller configuration — there's no nodrad.json config surface for them, mirroring how Modbus's own WriteSingleRegister isn't wired into its poller either:

cli := &opcua.Client{Endpoint: "opc.tcp://boiler-plc.local:4840", Timeout: 5 * time.Second}

// Write a single node's Value attribute.
status, err := cli.Write(ctx, opcua.NodeID{Namespace: 2, Numeric: 1001}, int32(72))

// Browse an address-space node's references.
refs, err := cli.Browse(ctx, opcua.NodeID{Namespace: 0, Numeric: 85}, 0, nil)

// Discovery services run over an unsecured pre-session channel, so
// they're package-level functions, not methods on an authenticated Client.
endpoints, err := opcua.GetEndpoints(ctx, "opc.tcp://boiler-plc.local:4840", 5*time.Second)
servers, err := opcua.FindServers(ctx, "opc.tcp://boiler-plc.local:4840", 5*time.Second)

Basic256Sha256 config scaffolding is in place (security_policy, security_mode, cert paths on the poller and Client.Security); full asymmetric secure-channel crypto remains a follow-up in ROADMAP.md — shipping a subtly-wrong "encrypted" channel would be worse than failing closed with a clear error when certs or crypto support are missing.

A protocol-agnostic passthrough connector for devices that don't speak Modbus/OPC-UA/J1939 — it opens a serial device and publishes each delimited (or idle-gap-framed) chunk of bytes as a Nodra event without decoding any application protocol. It shares Linux termios configuration with the Modbus RTU transport via internal/serialport rather than duplicating it, and is Linux-only for the same reason (a non-Linux build still compiles and registers the serial connector type; it only fails, with a clear error, when actually started).

{
  "type": "serial",
  "name": "sensor-line",
  "config": {
    "device": "/dev/ttyUSB0",
    "baud": 9600,
    "data_bits": 8,
    "parity": "none",
    "stop_bits": 1,
    "framing": "delimiter",
    "delimiter": "\n",
    "max_frame": 65536,
    "topic": "factory/sensor/raw",
    "timeout": "2s"
  }
}

framing is "delimiter" (default, split on the one-byte delimiter, itself defaulting to "\n") or "idle" (flush whatever's been read after idle_timeout of silence on the line, default 100ms). timeout is the reconnect backoff after an I/O error (e.g. device unplugged), default 2s — it is not a per-transaction deadline like Modbus's timeout, since this connector is a continuous read loop, not a request/response client. If no frame boundary shows up within max_frame bytes, the buffer is dropped (logged, reflected in connector health) rather than grown unboundedly — almost always a sign of a misconfigured delimiter or baud rate, not a legitimately huge frame.

The kernel/board is expected to own RS485 direction control, same as Modbus RTU — Nodra does not silently rewrite RS485 mode.