NODRA MODBUS RTU CONTRACT

Nodra Modbus RTU adapter contract

This file defines the integration seam for extending Nodra's existing modbus connector with an RTU transport. Nodra already has a dependency-free Modbus TCP client/poller; RTU should reuse the same connector/event path rather than create a second protocol stack. It is intentionally not implemented inside Device Agent.

Responsibility split

Device Agent
  "ttyS1 exists and this board declares it as RS485."

Nodra Modbus RTU adapter
  "slave 7, holding register 40021 is motor temperature = 82.3 C."

Device Agent supplies discovery from:

GET http://127.0.0.1:9188/api/v1/industrial/serial

Nodra should then open only a configured serial port.

Proposed Nodra RTU transport configuration

{
  "connectors": [
    {
      "type": "modbus",
      "name": "line-1-plc",
      "config": {
        "transport": "rtu",
        "serial": {
          "port": "/dev/ttyS1",
          "baud": 9600,
          "data_bits": 8,
          "parity": "even",
          "stop_bits": 1,
          "timeout_ms": 750,
          "inter_frame_delay_ms": 5
        },
        "polls": [
          {
            "unit": 7,
            "function": "holding-registers",
            "address": 20,
            "count": 2,
            "every_ms": 1000
          }
        ],
        "topic": "factory/line-1/plc-7/telemetry"
      }
    }
  ]
}

Adapter behavior

The Nodra transport extension should:

  1. verify the selected port is visible in Device Agent when Device Agent is available;
  2. never scan Modbus unit IDs by default;
  3. enforce one serial transaction at a time per physical port;
  4. implement Modbus RTU CRC16 and strict frame-length validation;
  5. preserve existing 0x03 holding-register behavior, add 0x04 input-register reads, and keep existing TCP 0x06 writes gated behind an explicit write capability for RTU;
  6. publish original sample time and polling latency;
  7. classify timeout, CRC, exception response and framing errors separately;
  8. write successful telemetry into Nodra's normal offline WAL path;
  9. expose adapter health without making Device Agent responsible for protocol health;
  10. back off on repeated failures rather than hammering a disconnected PLC.

Event example

{
  "adapter": "line-1-plc",
  "unit": 7,
  "event_time": "2026-09-11T13:30:00.123Z",
  "latency_ms": 18,
  "values": {
    "motor_temperature": 82.3,
    "motor_rpm": 1480
  }
}

Safety

Writes (0x05, 0x06, 0x0F, 0x10) should be a separate explicit capability and disabled by default. The first reference-hardware demo only needs reads.

Compatibility with the current Nodra connector

The current Nodra connectors/modbus package uses Modbus TCP framing and registers the connector type as modbus. Nodra agent configuration wraps connector-specific settings under connectors[].config. RTU should therefore be a transport choice under the same connector type. The polling loop should continue emitting connector.Event with the configured topic so Nodra's local routing, offline WAL, and downstream handling stay unchanged.